Programming Hard-Wired Zones
Each zone must be programmed into the system using the *56 Zone
Programming mode, which assigns characteristics that define the way the system
responds to faults on that zone. Refer to the Zone Response Type section and
the Zone Programming section for specific instructions on programming hard-
wired zones.
Check-Out Procedure For Hard-Wired Zones
After installation and programming of all hard-wired devices is completed, each
partition of the security system should be checked, as follows.
1. Make certain that all devices and sensors connected to the hard-wired zones
are not in a faulted state. Doors and windows with contacts should be closed,
PIRs should be covered (use a cloth to mask them temporarily if necessary).
2. Plug in the AC Transformer if you have not already done so.
3. With all hard-wired zones intact, the Alpha keypad connected to the system
should display:
DISARMED
READY TO ARM.
If the following is displayed,
DISARMED Press *
to show faults
press the [
*
] key to display the faulted zone(s). Restore any faulted zone(s) as
necessary (also make sure that you have connected a 2000 ohm EOL resistor
across the terminals of unused zones).
When the DISARMED...READY TO ARM message is displayed, you can
proceed to the next step.
4. Fault and then restore every contact or sensor on each zone individually to
ensure that it is being monitored by the system. Each time a zone is faulted,
the keypad should display the number of the faulted zone. When each zone is
restored, the READY TO ARM message should appear again.
If some hard-wired zones have been assigned to partition 1 and others to
partition 2, you will need to observe the keypad in the appropriate partition as
each zone in that partition is faulted and restored.
5. When you get the proper displays on the keypad(s), the hard-wired zones in
the system are functioning properly.
6. Unplug the AC transformer.