Section 4 - Data Field Programming
4-7
FIELD TITLE and DATA ENTRIES EXPLANATION
74
Low Bat Restore Report Code
0 = no report
For both digits: 1-9, A-F (Refer to table on
previous page
for method of programming
report codes.)
This is a 2-digit entry field.
This is sent when a system low battery condition is
restored to normal.
75
RF Xmtr. Low battery Restore Code
0 = no report
For both digits: 1-9, A-F (Refer to table on
previous page
for method of programming
report codes.)
This is a 2-digit entry field.
This is sent when a system low battery condition is
restored to normal.
Miscellaneous System Fields
80
Output Relays
Interactive mode
This Interactive Menu mode is applicable only if 4204
relays are to be used (3 in field
25).
Refer to
SECTION 6: Output Device Programming
for a
detailed programming procedure. Also refer to the
Output
Relays Worksheet for Fields
80 and
81
in the
Programming Form.
81
Zone Lists For Output Devices
Interactive mode
This mode is applicable if 4204 relays are to be used (3 in
field
25).
Refer to
SECTION 6: Output Device Programming
for a
detailed programming procedure. Also refer to
Zone Lists
for
Output Relays
in the Programming Form.
82
Custom Alpha Editing
Interactive mode
Refer to
SECTION 8: Alpha Descriptor Programming
for
procedure
.
91
Option Selection
0 = AAV unit
not
being used in system
4 = AAV unit is being used
8 = Exit Delay Restart
# + 12 = AAV + Exit Delay Restart
AAV should not be used when Paging or Alarm Reports
are being sent to a secondary number. If this is done, the
call to the secondary number by the communicator after
the Alarm Report will prevent the AAV from taking control
of the telephone line, and the AAV Listen-in session
cannot take place.
U
L
installations:
AAV option is not permitted (0).
92
Number of Reports in Armed Period
0 = limits number of reports to 10 or less
1 = allows an unlimited number of reports
This option limits the number of messages (Alarm and
Alarm Restore reports) sent to the central station in an
armed period.
U
L
installations:
no limit on number of reports (1).
93
Dynamic Signaling Delay (DSD)
(
1st entry
)
0 = disabled (both signals sent)
115 = entry times a 15-second delay.
e.g., 1 = 15 seconds, 2 = 30 seconds, etc.
Dynamic Signaling Priority (DSP)
(2nd entry)
0 = Primary phone number first;
1 = Long Range Radio (LRR) first.
This field (1st entry) lets you select the amount of time the
panel should wait for acknowledgment from the first
reporting destination before it attempts to send a message
to the second destination. Delays can be selected from 0 to
225 seconds, in 15-second increments. This delay is per
message.
If 0 is entered in this field, the control panel will send
redundant reports to both Primary phone number and
LRR.
U
L
installations:
must be set to 0 (in 1st entry).
The chart that follows provides a concise explanation of how the Dynamic signaling feature functions.
Vedere la pagina 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 79 80

Commenti su questo manuale

Nessun commento

Amana PTH073G25AXXX manuali

Manuali dei proprietari e guide per l'utente per no Amana PTH073G25AXXX.
We fornisce 1 manuali pdf Amana PTH073G25AXXX per scaricare gratuitamente in base al tipo di documento: Garanzia






Più prodotti e manuali per no Amana

Modelli Tipo di Documento
AFI2539ERW Guida all'Energia    Amana AFI2539ERW Energy Guide, 1 pagine
AMC4322GB Manuale di Installazione    Amana AMC4322GB Installation Instructions, 12 pagine
ABB2224BRW Guida all'Energia    Amana ABB2224BRW Energy Guide, 1 pagine
NTC3500FW Guida all'Energia   Amana NTC3500FW Energy Guide [en] , 1 pagine
WS916D1 Manuale di Installazione   Amana WS900D-INTERNAL Installation Instructions [ko] , 4 pagine
ABB1924BRW Garanzia      Amana ABB1924BRW Warranty, 6 pagine
AWO6317SFS Dimensioni della Guida   Amana AWO6317SFS AWO6317SFS Dimension Guide EN, 2 pagine
ABB1924BRW Guida all'Energia    Amana ABB1924BRW Energy Guide (109.20 KB), 1 pagine
ADB1500ADS Garanzia      Amana ADB1500ADS Warranty, 3 pagine
PBH092G12CB Manuale di Servizio   Amana PBH093G35CC Technical Manual, 18 pagine
AEP222VAW Dimensioni della Guida   Amana AEP222VAW Dimension Guide (207.67 KB), 1 pagine
PTSB420E Manuale di Installazione   Amana PTSB420E Installation Instructions [pt] , 2 pagine
NTW4516FW Scheda delle Specifiche   Amana NTW4516FW Specifications Sheet, 2 pagine
AE183E35AXAA Manuale del Proprietario   Amana AE183E35AXAA Owner's Manual, 24 pagine
AMV6507RGS Manuale di Installazione   Amana AMV6507RGS AMV6507RGS Installation Instruction EN, 12 pagine
AGR4230BAB Garanzia   Amana AGR4230BAB Warranty (57.00 KB), 2 pagine
ADB1400AGW Guida all'Energia    Amana ADB1400AGW Energy Guide, 2 pagine
ASI2175GRB Guida all'Energia   Amana ASI2175GRB Energy Guide, 1 pagine
AMAP061BW Garanzia   Amana AMAP061BW Warranty, 1 pagine
AMAP061BW Manuale del Proprietario     Amana AMAP061BW Owner's Manual, 68 pagine