ADEMCO Vista-20HW Guida alla Risoluzione dei Problemi Pagina 22

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 100
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 21
Turning Off Fire Alarm You can turn off Fire alarm sounding by pressing the OFF key on any keypad or
Sounding
other arming/disarming device in that partition. To clear the “memory of alarm”
and to reset the detector’s alarm, enter the security code plus OFF again.
b
Compatible 2-Wire Smoke Detectors
Detector Type
Device Model #
v
Photoelectricw/heatsensor,directwire
SystemSensor2300T
Photoelectric,directwire
SystemSensor2400
Photoelectricw/heatsensor,directwire
SystemSensor2400TH
Photoelectricw/B401Bbase
SystemSensor2451
Photoelectricw/heatsensor& B401Bbase
SystemSensor2451TH
Ionization,directwire
SystemSensor1400
Ionizationw/IMOIBbase
SystemSensor1451
PhotoelectricductdetectorwLDH400base
SystemSensor2451
Ionizationductdetect.wiDH400base
SystemSensor1451DH
r
---------
1
2-WIRE SMOKE UJ
z
L---------J
IN ULINSTALLATIONS,ONLY ZONE 1
MAY BE USEO FOR FIRE.
Figure 7. 2-Wine Smoke Detector Connected to Zone 1
Wdng 4-W- SmokdCombuetion Detectors on Zones 2-7
The system will support as many 4-wire detectors as can be powered from
Auxiliary Power on the control on zones 2-7. Refer to the detector’s
instructions for complete details regarding its proper installation and
w
operation.
1.
2.
Connect 12 volt power for the detectors horn Auxiliary Power terminals 4
and 5, (which will interrupt power for fire alarm reset). Observe proper
polarity when connecting detectors.
Connect detectors (includirw heat detectors. if used) across terminals of
the zone selected (zones 2-7”may be used). W dete~rs must be wired in
parallel.
3. To supervise power, we recommend the use of a System Sensor
No. A77-716B supervisory module.
F@re 8. 4-wire Smoke Detector Connection (Zonee 2-7)
-22-
Vedere la pagina 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 99 100

Commenti su questo manuale

Nessun commento